You have to know by now, that expansion valves and devices in air conditioning systems have the function of,
allowing pressure build up from the compressor’s outlet, and hence separating the high pressure and low pressure sides of an air conditioner, and
regulating the flow of liquid refrigerant, into expansion zone. Too much liquid into expansion zone is not good. Too little is just as bad
It is a form of flow limitation device to enable pressure drop across the inlet and outlet lines, as explained here.
So, what is too much and too little of flow?
It depends on the size of the evaporator and refrigerant type used.
The evaporator and refrigerant are matched to give desired heat removal capacity of an air conditioning unit. Therefore, the expansion device has to make sure that the amount of liquid fed into the expansion zone, will be completely boiled at the end of the evaporator.
Anything less than that, is too little. Anything beyond it, is too much.
The common types of expansion valves or devices:
The,
capillary tube, and
the thermostatic expansion valve
are the most commonly used in air conditioning systems. The former is normally used in small sized units, and the latter is used in larger sized units.
The capillary tube expansion device
This device is not a valve, but a plain tube with similar material to the main air conditioner tubing.
There is no device to control the flow, except for the tube’s internal diameter, length and its spiral shape.
These factors will create necessary restriction, and allowing necessary amount of refrigerant into expansion zone.
Thermostatic expansion valves
Now, this is a valve with moving parts involved.
The valve will have a,
sensing bulb connected to a tube,
diaphragm,
spring loaded valve seat,
liquid inlet line,
liquid outlet line,
filter at the inlet line
adjusting knob
These expansion valves will have the sensing bulb placed at the exit line of the evaporator.
Pressure within the connected tube will rise if the exit temperature is too high, i.e. when there is insufficient boiling within the evaporator.
Pressure in the connected tube will drop if the exit temperature is too low, i.e. there is too much fluid going into the evaporator.
The rise and drop in pressure will push, or pull the diaphragm. This diaphragm is directly connected to the spring loaded valve seat. The seat is arranged such that it will increase flow under high pressure, and vice versa.
Therefore, these expansion valves may operate under varying load conditions.
Filter is used to trap unnecessary solids from equipment wear and tear, into the valve seat of the expansion valves.
Adjusting knob or dial, is used to tune the valves so that there will be approximately extra 5 oC (41 oF) of refrigerant superheat at the evaporator’s exit. Liquid flooding into the compressor will be avoided by such setting.
Comparison between thermostatic expansion valves and capillary tubes:
Capillary tube
TEV
Advantages
Cheap, simple design, maintenance free
Can operate under varying load requirements
Disadvantages
May operate under tight load variations only. Consider tube replacement from compressor’s exit to evaporator’s inlet, if defective
More expensive than capillary tubes. Requires tuning during first assembly